Key Takeaways
- Bomba's requirements for a factory or warehouse come from the Uniform Building By-Laws (UBBL). The Tenth Schedule sets which systems a building needs by use and floor area, and the by-laws tie each system to a Malaysian Standard: sprinklers to MS 1910, hose reels and hydrants to MS 1489, portable extinguishers to MS 1539 and fire alarms to MS 1745.
- Sprinklers start above 2,000 m² for a single-storey factory. Under Selangor's gazetted table (Sel. P.U. 142/2012), a single-storey factory above 2,000 m² (21,528 sq ft), a two-storey factory above 1,000 m² per floor and a single-storey warehouse of combustible goods above 1,000 m² or 7,000 m³ all need sprinklers as well as hose reels.
- Every building needs a fire hydrant close by. Selangor's by-law 225(2) requires at least one hydrant within 45 m of the fire brigade access, with hydrants no more than 90 m apart. The 2021 model by-laws tighten this to 30 m from an entry or breeching inlet.
- A fire system that is missing or not working is a "fire-hazard" under the Fire Services Act 1988. Bomba serves the abatement notice on the occupier when the occupier caused the problem, otherwise on the owner. Ignoring it can mean a fine of up to RM5,000, up to 3 years' jail, or both, plus RM100 for every further day.
- Since 3 February 2026, only a Bomba-registered competent person or fire safety contractor may install, test, service, recharge or repair prescribed fire equipment, and 28 listed products, from sprinklers and hose reels to alarm panels and fire pumps, must be registered before they are sold or installed. In a tenancy, the Act decides whom Bomba pursues; the lease decides who pays.
A factory or warehouse in Malaysia needs the fire protection that the Tenth Schedule of the Uniform Building By-Laws sets for its use and size: portable extinguishers in every building, hose reels once the floor area passes 750 m² or 1,000 m² (depending on the version that applies), automatic sprinklers once a single-storey factory passes 2,000 m² or a combustible-goods warehouse passes 1,000 m², pressurised hydrants for very large and high-risk sites, and alarms that grow from a manual bell to automatic detection and a monitored link to the fire station. Bomba (JBPM, the Fire and Rescue Department of Malaysia) receives the fire installation plans before work starts and can act against the owner or occupier if the systems are not kept working.
This guide goes system by system. For the annual fire certificate itself (which premises need one, fees and renewal), read our Bomba fire certificate guide for factories and warehouses. This guide explains the law and is not legal advice: your M&E engineer and Bomba decide what a particular building needs.
Which rules decide the fire protection in a factory or warehouse?
Three layers apply, and it helps to know which one answers which question.
- The Uniform Building By-Laws (UBBL), made under the Street, Drainage and Building Act 1974, decide what a building must have. Each state gazettes its own version. The Local Government Department (JKT) of the housing ministry publishes a consolidated UBBL with the 2021 amendments, but warns that it "is only a model by-law. Only the Uniform Building By-Laws of each respective state has empowerment powers." On JKT's list of state gazettes, Selangor's latest amendment is Sel. P.U. 142/2012, in force from 27 December 2012, which replaced the Tenth Schedule. Ask the council (MBSA, MBDK, MBSJ, MPKj and so on) which version your building was approved under.
- Malaysian Standards decide how each system is designed and installed.
- The Fire Services Act 1988 (Act 341) decides who answers for keeping it working, who needs a fire certificate and, since 2026, who may service the equipment.
| System | UBBL by-law | Malaysian Standard | When it applies |
|---|---|---|---|
| Portable fire extinguishers | 227 | MS 1539 | All buildings |
| Hose reel system | 226A | MS 1489 | As the Tenth Schedule sets |
| Automatic sprinkler system | 228 | MS 1910 | As the Tenth Schedule sets |
| External fire hydrant | 225(2) | MS 1489 | Every building |
| Fire detection and alarm | 237 | MS 1745 | As the Tenth Schedule sets |
| Dry riser / wet riser | 230 / 231 | MS 1489 | Topmost floor more than 18 m / 30 m above fire appliance access level (2021 text) |
| Emergency lighting | 253A | MS 619, MS 2687 | At least 3 hours of light on power failure (2021 text) |
Selangor's by-laws cite the same standards for hydrants, hose reels, extinguishers, sprinklers and alarms. Under by-law 245(2) of both versions, the plans, drawings and calculations of all fire fighting installations go to Bomba before work starts.
When is a sprinkler system required in a factory?
This is the question most owners and tenants ask first. The table compares Selangor's gazetted Tenth Schedule (Sel. P.U. 142/2012) with the 2021 model text. Floor areas are total floor area unless stated; 1 m² is 10.764 sq ft.
| Factory type | Selangor 2012 table | 2021 model table |
|---|---|---|
| Single storey, below 750 m² (8,073 sq ft) | None | None |
| Single storey, 750 to 1,000 m² | 25 kg trolley extinguishers | Hose reel |
| Single storey, 1,001 to 2,000 m² | Hose reel | Hose reel |
| Single storey, above 2,000 m² (21,528 sq ft) | Hose reel + sprinklers | Sprinklers + hose reel |
| Two storeys, each floor a separate compartment, below 500 m² per floor | 25 kg trolley extinguishers | None |
| Two storeys, 500 to 1,000 m² per floor | Hose reel | Hose reel |
| Two storeys, above 1,000 m² per floor | Hose reel + sprinklers | Sprinklers + hose reel |
| Flatted factory block, above 1,000 m² per compartment or floor | Hose reel + sprinklers | Sprinklers + hose reel (also above 7,000 m³ per compartment) |
| Open-structure steel or metal fabrication | None | None |
| Sawmill or steel mill | Hose reel + pressurised hydrant | Hose reel + pressurised hydrant |
| Vehicle assembly, 2,001 to 5,000 m² | Hose reel + pressurised hydrant | Hose reel + pressurised hydrant |
| Vehicle assembly, above 5,000 m² (53,820 sq ft) | Hose reel, sprinklers, pressurised hydrant | Sprinklers, hose reel, pressurised hydrant |
| Palm oil mill, refinery, sugar mill, cement works | Hose reel + pressurised hydrant | Hose reel + pressurised hydrant |
| Wet process | Hose reel | Hose reel |
| Hazardous process | As Bomba requires (hose reel, sprinklers, gas or hydrant) | As Bomba requires (sprinklers, water spray, foam, gas, other automatic systems, hose reel, hydrant) |
Sources: Tenth Schedule of Sel. P.U. 142/2012 and of the JKT consolidated UBBL (2021). Both add that a factory operating after dark must have the emergency lighting Bomba requires, and that a special risk, hazardous process or hazardous storage must have the fire protection Bomba requires.
Two rules are worth knowing before you plan a layout:
- Sprinklers can let you build bigger compartments. By-law 136 in both versions says that where a building has an automatic sprinkler installation complying with MS 1910, the compartment size limits are treated as doubled. For a large open warehouse this can be the difference between one floor plate and several fire walls.
- Hazardous rooms count even inside an ordinary factory. Note 1 of the Tenth Schedule lists boiler rooms and fuel stores, repair shops, transformer and switch rooms, plant rooms, indoor storage of flammable liquids, chemical plants and process equipment rooms. By-law 226 requires any automatic system there to suit the hazardous material.
What does a warehouse need: combustible or non-combustible goods?
Warehouses are judged on volume as well as floor area, and on what is stored. A higher roof reaches the cubic-metre lines sooner.
| Warehouse | Selangor 2012 table | 2021 model table |
|---|---|---|
| Non-combustible goods (e.g. clay, bleaching earth), single storey, below 2,000 m² | None | None |
| Non-combustible goods, above 2,000 m² or two storeys and above | Hose reel | Hose reel |
| Combustible goods, single storey, below 250 m² | None | None |
| Combustible goods, single storey, 250 to 500 m² | Portable extinguishers | None (manual alarm) |
| Combustible goods, single storey, 501 to 1,000 m² and below 7,000 m³ | Hose reel | Hose reel |
| Combustible goods, single storey, above 1,000 m² or 7,000 m³ | Hose reel + sprinklers | Sprinklers + hose reel (1,001 to 10,000 m² and 7,001 to 70,000 m³) |
| Combustible goods, single storey, above 10,000 m² or 70,000 m³ | Hose reel + sprinklers | Sprinklers, hose reel and pressurised hydrant |
| Combustible goods, open sided, above 1,000 m² | Hose reel | Hose reel |
| Combustible goods, two storeys and above, above 1,000 m² or 7,000 m³ | Hose reel + sprinklers | Sprinklers + hose reel |
A sprinkler system is designed for a stated hazard and storage height. If you plan to rack higher or store more combustible goods than the building was designed for, ask for the M&E design basis before you sign. Our partner Ms Teh's guide to pallet racking, floor loading and Bomba checks in Klang warehouses covers the racking side, and our floor loading calculator checks the slab. Chemicals and flammable liquids are covered in our guide to renting a warehouse for chemical storage.
Hose reels, hydrants and risers: the distance rules
Hose reels. By-law 226A calls for hose reels designed to MS 1489. A PAM briefing on the 2021 amendments by the Malaysian Institute of Architects summarises the coverage rule as a 30 m radius per hose reel, with reels no more than 48 m apart, so every part of the floor is reachable. Racking, mezzanines and new walls can leave corners outside that reach.
External hydrants. Every building must be served by at least one hydrant:
| Version | Hydrant distance rule |
|---|---|
| Selangor (Sel. P.U. 142/2012) | Within 45 m of the fire brigade access; hydrants not more than 90 m apart |
| 2021 model text | Within 30 m of an entry to the building or a breeching inlet; hydrants not more than 90 m apart |
In both, Bomba may require additional hydrants depending on the size, location and fire appliance access of the building. This hydrant on the road or in the compound is different from the "pressurised hydrant system" in the tables above, which is a pumped hydrant ring for high-risk sites.
What the Fire Services Act says about hydrants. Under Act 341:
- Section 23: anyone other than the water authority must give the State Director of Bomba written notice at least seven days before works that affect a hydrant or its water flow, and must leave the hydrant in good working condition afterwards. Works that affect access to a hydrant count.
- Section 26: covering up, enclosing or concealing a hydrant, tampering with it, or using it for anything other than fire fighting is an offence. Parking containers or stacking pallets over a hydrant, or tapping it to wash the yard, falls on the wrong side of this.
- Section 22: Bomba may direct the owner or person in control of premises in writing to provide water storage for fire fighting, and failing to comply is an offence.
Risers. A dry riser is needed when the topmost occupied floor is more than 18 m above the fire appliance access level, and a wet riser above 30 m (by-laws 230 and 231, 2021 text). Most single-storey factories never reach this; multi-storey flatted factories and ramp-up warehouses can.
Fire installation pipes are painted red (by-law 248), and cabinets for hose reels and extinguishers must be clearly marked.
Fire alarms, detection, monitoring and emergency power
The alarm column of the Tenth Schedule grows with size. In the 2021 model table, a single-storey factory of 750 to 1,000 m² needs a manual electric fire alarm; 1,001 to 2,000 m² adds automatic fire detection; above 2,000 m² it needs a manual alarm, a public address system and an automatic fire monitoring system, which by-law 238 describes as connected to the appropriate fire station. Combustible-goods warehouses above 1,000 m² need a manual alarm and automatic monitoring.
Other by-laws that matter in large sheds (2021 text):
- Electrical isolation switch (by-law 240): any building with more than 1,000 m² per floor needs a switch complying with IEC 60947-3 so firefighters can cut power to the floor.
- Emergency power (by-law 253): fire pumps, fire alarms, smoke control and emergency lighting must run on an emergency supply that takes over within 60 seconds, from a battery (at least 1.5 hours) or a generator set with automatic start.
- Emergency lighting (by-law 253A): at least 3 hours of illumination for escape.
- Fire doors (by-laws 162 and 164): openings in compartment walls need fire doors of the right fire resistance, fitted with automatic closers. A fire door may be held open only by a device that releases on heat, and not on a door to a protected corridor or exit staircase.
Who can install and service fire systems from 2026?
The Fire Services (Amendment) Act 2025 (Act A1764) created a Bomba register. Its key sections for occupiers:
- Section 36D: no person may install, test, service, recharge or repair prescribed fire equipment unless registered as a competent person in the right category or as a fire safety contractor. Penalty: a fine of up to RM50,000, up to 3 years' jail, or both.
- Section 36K: prescribed equipment may not be installed, or sold for installation, at any premises unless it is registered. Penalty: a fine of up to RM500,000, up to 5 years' jail, or both.
The Fire Services (Competent Person and Fire Safety Contractor) Regulations 2026, P.U.(A) 39/2026, in force since 3 February 2026, set three categories of competent person and match them to equipment:
| Equipment | Competent person category |
|---|---|
| Fire extinguisher | Fixed or portable installation |
| Fire suppression system (gas) | Fixed or portable installation |
| Fire alarm panel | Mechanical or electrical |
| Fire-fighting system pump | Mechanical or electrical |
| Fire roller shutter | Mechanical or electrical |
A fire safety contractor must be a company, partnership or LLP with the facilities to do the work and at least one registered competent person on staff. A certificate of registration costs RM100 until 31 December 2026; from 1 January 2027 it costs RM600 for the mechanical or electrical and civil or structural categories, RM500 for the fixed or portable installation category and RM1,000 for a contractor, with renewals of RM300 to RM500. People already doing this work before 3 February 2026 have one year from that date to register as competent persons under the transitional rule.
The companion P.U.(A) 46/2026 lists 28 products that must be registered with Bomba (RM500 per application), each against its standard. They include the fire hose reel (MS 1447, MS 1488), automatic sprinkler system (UL 199), fire-fighting system pump (MS 2616), fire alarm panel (MS 1745), smoke and heat detectors, manual fire alarms, alarm bells, fire extinguishers (MS 1539), fire resistant doors, fire roller shutters, emergency lights and exit signs.
What this means in practice: when you appoint or renew a maintenance contract, ask for the contractor's Bomba certificate of registration and keep it with the service records. When equipment is replaced during a fit-out, ask for proof that the product is registered.
Fire safety managers from 2027. Section 27A of Act 341, added in 2018 by Act A1568, requires the owner, occupier or management of a designated premises to set up a fire safety organisation, with a fine of up to RM50,000, up to 5 years' jail, or both for failing to. JBPM's director-general said owners of 9,451 designated buildings must appoint Fire Safety Managers and Fire Safety Officers from 1 April 2027, and that FSM-prepared annual inspection reports would in future support fire certificate renewal (Malay Mail, 6 October 2026).
Who pays for fire protection in a rented factory or warehouse?
No statute splits the bill between landlord and tenant. The Fire Services Act decides whom Bomba holds responsible, and the tenancy agreement decides who pays. Start with what the Act says:
| Duty | Who the Act names | Section |
|---|---|---|
| Abate a fire-hazard (missing or not-working fire equipment, blocked exits) | The occupier, if the hazard arose from the occupier's act or default; otherwise the owner; the occupier again if the owner cannot be found | s.8 |
| Hold a fire certificate for a designated premises | The owner commits the offence if none is in force (fine up to RM50,000, up to 5 years, or both) | s.33 |
| Notify Bomba before a material change | The occupier, before work starts | s.32(2) |
| Set up a fire safety organisation | Owner, occupier or person in overall management | s.27A |
| Submit fire installation plans to Bomba | The by-law names no party; the plans must go in before work starts | UBBL by-law 245(2) |
Section 2 of the Act defines "fire-hazard" to include the removal or absence of fire-fighting equipment required by law, and equipment installed under any written law or as required by Bomba that is "not in efficient working order". Section 10 makes failing to comply with an abatement notice an offence.
A lease that follows the same logic is easier to defend: the cost follows the cause. Points to settle in writing before you sign (our tenancy agreement template guide shows where they sit):
| Item | Question to settle in the lease |
|---|---|
| Base-building systems at handover (sprinklers, hydrant ring, pumps, tanks, alarm panel) | Are they handed over working, with a recent test report? Who replaces a pump or panel at the end of its life? |
| Routine servicing | Who appoints the registered contractor, pays the contract and keeps the logbook? |
| Extinguishers and hose reels inside the unit | Who services and replaces them? |
| Upgrades Bomba orders | Who pays when the cause is the building (age, a change in the by-laws) versus the tenant's use (new process, higher racking, chemicals)? |
| Tenant fit-out | Tenant to bear the design, Bomba submission and any extra sprinklers, detectors or hose reels its partitions, offices or racking need |
| Fire certificate and fire safety organisation | Who files the renewal, who arranges the inspection, who appoints the Fire Safety Manager? |
| Insurance | Does the fire policy require the systems to be kept in working order? See our guide to factory insurance for landlords and tenants |
What to check before you rent or buy
| Check | What to ask for | Red flag |
|---|---|---|
| Which table applied | The approved fire installation plans and the year of approval | Plans that do not match the building on site |
| Sprinkler system | Last test report, pump set left on automatic, main valves open | Isolated valves, pumps on manual, rusted heads |
| Hose reels and hydrants | Coverage drawing, pressure test, clear access | Reels behind racking, hydrant blocked by containers |
| Alarm and monitoring | Panel free of fault signals, monitoring link active | Silenced panel or disconnected monitoring |
| Service contractor | Bomba certificate of registration (from 2026) | Contractor cannot show registration |
| Your use against the design | Your goods, racking height and any chemicals against the design basis | Racking planned above the design storage height |
| Who pays | Clauses on servicing, upgrades and fit-out | Lease silent, or every upgrade pushed to one side |
For the wider pre-signing checklist, see what to check before renting a factory. If you need height for racking, shortlist from high-ceiling factories for rent in Selangor and confirm the sprinkler design matches your stacking, not only the clear height.
Practical steps: more questions
Who can service fire pumps, alarm panels and extinguishers from 2026?
Only a person registered with Bomba as a competent person in the matching category, or a registered fire safety contractor, under section 36D of the Fire Services Act and P.U.(A) 39/2026. Working without registration carries a fine of up to RM50,000, up to 3 years' jail, or both. Ask your contractor for the certificate of registration.
Frequently Asked Questions
Does every factory need Bomba approval?
Yes, in two ways. Every new factory's fire installation drawings go to Bomba for endorsement before work starts, and the building must keep the fire systems the Uniform Building By-Laws set for its size. On top of that, designated premises, such as a sprinklered factory of 2,000 m² or more or one with a hazardous process, need an annual fire certificate. Councils also ask for Bomba's letter before licensing work with flammable materials, and a tenant must tell Bomba before a material change such as storing chemicals.
What are the Bomba requirements for a factory in Malaysia?
A factory must have the fire systems the Tenth Schedule of the Uniform Building By-Laws sets for its type and floor area, designed to the Malaysian Standards the by-laws name, with the plans submitted to Bomba before installation. Every building needs portable extinguishers and a nearby hydrant; hose reels, sprinklers, alarms and automatic monitoring are added as the floor area grows. A sprinklered factory of 2,000 m² or more is also a designated premises that needs an annual fire certificate, as our fire certificate guide explains.
What are the sprinkler requirements in Malaysia?
Under Selangor's gazetted table, sprinklers are required in a single-storey factory above 2,000 m², a two-storey factory above 1,000 m² per floor, vehicle assembly plants above 5,000 m² and single-storey warehouses of combustible goods above 1,000 m² or 7,000 m³. Sprinklers are designed and installed to MS 1910, and a hazardous process or storage needs whatever automatic system Bomba requires for that material.
What are the Bomba requirements for fire extinguishers in Malaysia?
By-law 227 requires portable fire extinguishers in all buildings in accordance with MS 1539, so the type, number and positions come from that standard as your M&E designer applies it to the floor plan. Selangor's table also calls for 25 kg trolley extinguishers in single-storey factories of 750 to 1,000 m². Since 3 February 2026, extinguishers must be serviced and recharged by a Bomba-registered competent person in the fixed or portable installation category.
What is the standard distance between fire hydrants?
Hydrants must be no more than 90 m apart. In Selangor's by-laws the building must have at least one hydrant within 45 m of the fire brigade access; the 2021 model text sets 30 m from an entry to the building or a breeching inlet. Bomba can require additional hydrants for large sites.
What is the hose reel requirement in Malaysia?
Hose reels are required by the Tenth Schedule according to building type and floor area, and are designed to MS 1489. The rule of thumb in the PAM briefing on the 2021 amendments is a 30 m radius of coverage per reel, with reels no more than 48 m apart, so every part of the floor can be reached.
Who pays for fire safety maintenance in a rented factory, the landlord or the tenant?
The law does not split the cost; the tenancy agreement does. The Fire Services Act lets Bomba serve a notice on the tenant when the tenant caused the defect and on the owner otherwise, and the owner is liable if a designated premises has no fire certificate. Agree in writing who services the systems, who pays for upgrades Bomba orders and who pays for changes caused by the tenant's fit-out.
Can a tenant change the sprinklers or fire alarm layout?
Not on their own initiative. Plans for fire installations must be submitted to Bomba before work starts (by-law 245(2)), and in a designated premises the occupier must notify Bomba before any material change (section 32(2) of Act 341). Since 2026 the work must be done by a registered competent person or fire safety contractor using registered equipment.