Key Takeaways

  • Every storey of a factory needs at least two separate exits, and every fire compartment needs at least two storey exits placed at least 5 m apart. Larger floors need more, because every worker must reach an exit within the travel distance limit.
  • Travel distance for a general factory is 30 m without sprinklers and 60 m with sprinklers, with a 15 m dead end. A high hazard factory is limited to 22 m (35 m sprinklered) and allows no dead end at all, under the Seventh Schedule of the Selangor Uniform Building By-Laws.
  • Exit width follows the head count. Factory floors are counted at 10 m² gross per person, exits are measured in units of 550 mm, one unit serves 100 people through doors to the outside or 60 people down stairs, and no access to an exit may be narrower than 700 mm.
  • Exit doors must open from inside without a key, exit signs and emergency lights must meet the Malaysian Standards the by-laws name, and from 3 February 2026 exit signs, emergency lights and fire resistant doors must be products registered with Bomba.
  • When fire safety falls short, Bomba acts under the Fire Services Act 1988: a notice to fix within a set time, then fines, Bomba doing the work at your cost, or a court order closing or restricting the premises. There is no official price list for upgrades; the cost depends on the building and what is missing.

A factory in Selangor needs at least two separate exits from each storey, placed so that nobody walks further than the Seventh Schedule allows, wide enough for the number of people on that floor, with doors that open without a key, lit and signed so people can find them in smoke or a power cut. These rules sit in Part VII of the Uniform Building By-Laws (UBBL), and Bomba (the Fire and Rescue Department of Malaysia, JBPM) enforces them through the Fire Services Act 1988.

This guide covers the escape side: exits, travel distance, widths, doors, signs, lighting and upper floors, then what happens when a factory fails and what drives the cost of putting it right. The sprinklers, hose reels, hydrants and alarms each size of factory needs are covered in our Bomba fire protection guide for factories and warehouses, and the annual certificate in our fire certificate guide. This guide explains the by-laws and the Act and is not legal advice: your architect or engineer and Bomba decide what a particular building needs.

Which version applies? Selangor's gazetted by-laws are the Selangor Uniform Building By-Laws 1986 as updated by JKT, including the amendments of Sel. P.U. 142/2012. The Local Government Department (JKT) also publishes a consolidated UBBL with the 2021 amendments, which it describes as "only a model by-law"; only each state's by-laws can be enforced. This guide quotes Selangor first and notes where the 2021 text differs. Ask the council which version your building was approved under.

How many emergency exits does a factory need?

At least two separate exits from every storey, and at least two storey exits from every fire compartment, placed at least 5 m apart. You need more when the floor is too big for every worker to reach an exit within the travel distance (30 m, or 60 m with sprinklers, for a general factory) or when the exits are too narrow for the number of people.

The by-laws that set the number

Rule Selangor by-law What it says
Exits per storey 166(1) Not less than two separate exits from each storey, plus any more that are needed
Exits within reach 166(2) Exits sited so they are within the Seventh Schedule travel distance and readily accessible at all times
Exits per compartment 167(1) Every compartment has at least two storey exits, as far apart as practical and not less than 5 m apart
Spacing 174(1) Where two or more storey exits are required, at least 5 m apart measured between the nearest edges of the openings
Where an exit leads 174(2) Directly to a final exit, to a protected staircase that ends at a final exit, or to an external route that ends at a final exit
Upper floors 168(1) Every upper floor has at least two separate staircases, except where by-law 194 allows one

So the count is never "one per X square feet". The designer starts at two per storey and per compartment, then adds exits until both tests below pass: every point on the floor is within the travel distance, and the exits together are wide enough for the floor's occupant load.

Can a factory have only one staircase?

Rarely in Selangor. Selangor's by-law 194 (as substituted in 2012) allows a single staircase only in dwellings up to 12 m and in shophouses or dwellings of not more than two storeys, or with the first storey not more than 6 m above ground. The 2021 model text widens this to "any building" of not more than two storeys whose first floor is not more than 6 m above the ground floor. If you are looking at a 1.5 or 2 storey factory with one internal staircase to the office, ask which rule it was approved under before you plan more people upstairs.

How far can workers walk to an exit in a factory?

The Seventh Schedule sets the longest walk from any point on the floor to the nearest storey exit, and a shorter limit for a dead end (a corridor or aisle where you can only go one way).

Use (Seventh Schedule) Dead end limit Without sprinklers With sprinklers
Factory, general and special purpose 15 m 30 m (about 98 ft) 60 m (about 197 ft)
Factory, high hazard 0 m 22 m 35 m
Factory, open structure No requirement No requirement No requirement
Storage, low and ordinary hazard 15 m 30 m 60 m
Storage, high hazard 10 m 20 m 35 m
Office 15 m 45 m 75 m (60 m in the 2021 text)

How the distance is measured (by-law 165):

  1. Along the natural path of travel on the floor, starting 0.3 m from the most remote point, keeping 0.3 m clear of corners and obstructions, and ending at the storey exit. Racking, machines and partitions therefore lengthen the walk.
  2. In open areas the straight line distance to an exit may not exceed two thirds of the permitted travel distance: 20 m in an unsprinklered general factory, 40 m in a sprinklered one.
  3. In a room of not more than six people, Selangor measures from the room door if the room is not more than 15 m² (the 2021 text uses a 9 m walk inside the room instead).

A note to the schedule allows very large undivided single storey floors, such as assembly halls, to exceed the normal limits only with complete automatic sprinkler protection and ceiling, curtain board and roof ventilation designed to keep smoke above 1.8 m long enough, and never beyond 120 m to the nearest exit.

Why sprinklers matter here: in Selangor's Tenth Schedule a single storey factory above 2,000 m² (21,528 sq ft) already needs sprinklers. That same installation doubles the travel distance allowance from 30 m to 60 m, which is often what lets a large shed work with exits only on its outer walls.

How wide must factory exits, doors and staircases be?

Width comes from the number of people the floor is designed for, worked out with the Seventh Schedule (by-laws 175 to 177 and 181).

Item Rule
Occupant load, factory 10 m² gross floor area per person
Occupant load, office 10 m² gross per person
Occupant load, warehouse 30 m² gross per person (2021 text; Selangor's 2012 table lists storage and shipping under shops at 10 m²)
Unit of exit width 550 mm (by-law 181 in Selangor's text says 552 mm)
Part units Fractions are not counted, except that 300 mm added to one or more full units counts as half a unit
Smallest access to an exit 700 mm
Capacity of one unit, factory 100 persons through doors to the outside, horizontal exits or main ramps; 60 persons on stairs
Door width counted Only the clear width with the door open
Staircase width Clear width between walls; handrails may intrude up to 80 mm; width kept through landings, and door swings must not cut into it
Staircase redundancy Assume one staircase is unavailable; the others must carry the load of the busiest floor
Smallest staircase At least one staircase of two units (1,100 mm), but 900 mm is allowed where all floors it serves hold fewer than 50 people
Along the route No exit route may get narrower on the way to the final exit; where routes merge, the common exit must be at least as wide as their sum

Worked examples (to show the arithmetic only)

These are illustrations of how the by-laws work, not a design. Your architect or engineer measures the real layout.

  1. Single storey factory, 1,500 m² (about 16,150 sq ft), no sprinklers. Occupant load 1,500 / 10 = 150 people, so 1.5 units of exit width (150 / 100) are needed. Two doors that each give at least 700 mm of clear width count as one unit each, which covers it. Distance is usually the harder test: in a 50 m by 30 m shed, exits only at one short end leave the far end about 50 m away, above the 30 m limit, so exits are needed on more than one wall.
  2. Single storey factory, 3,000 m², sprinklered (as Selangor requires above 2,000 m²). Occupant load 300 people, so at least 3 units (1,650 mm of clear door width in total) split across at least two exits 5 m or more apart, with every point within 60 m of an exit and within 40 m in a straight line.
  3. Upstairs office of 300 m² in a 1.5 storey factory. Occupant load 30 people, one unit on stairs (60 per unit). Because fewer than 50 people use the stairs, a 900 mm staircase is allowed, but Selangor's text still asks for two separate staircases from an upper floor unless the single staircase exception applies.
Workers walking along clear aisles to two separate exit doors in a factory
IllustrationWorkers walking along clear aisles to two separate exit doors in a factory

What do the exit doors, signs and emergency lights need?

Exit doors

  • All exit doors must be openable from the inside without a key or any special knowledge or effort (by-law 173(1)). A padlocked side door or a chained gate fails this.
  • Exit doors must close automatically when released, and all door devices, including magnetic holders, must release the doors on power failure or when the fire alarm activates (by-law 173(2)).
  • A power operated door counts as a means of escape only if it can be swung open by hand in the direction of exit travel (by-law 193). Ask your designer before counting a motorised loading bay shutter as one of your exits.

Fire doors

Openings in compartment walls need fire doors with the fire resistance the Ninth Schedule sets for that wall, openings into a protected corridor or lobby need half hour fire doors (by-law 162), doors and frames are built to MS 1073 (by-law 163), and every fire door has an automatic closer. A fire door may be held open only by a device that releases on heat, and never on a door protecting a protected corridor or staircase (by-law 164). Wedging fire doors open defeats all of this.

Exit signs

Selangor's by-law 172(3), as substituted in 2012, requires every emergency exit sign to be designed and installed to MS 983 and MS 619. The 2021 model text spells out the rest: storey exits and the way to them marked by readily visible signs that decorations, furnishings or equipment must not hide; a "KELUAR" sign with an arrow wherever the way to the nearest exit is not obvious; signs to MS 2687 and MS 619; and signs lit continuously while the building is occupied. In a warehouse, check the signs again after every racking change.

Emergency lighting and power

  • Selangor's by-law 253A requires emergency lighting for escape, self-contained to MS 619 or fed from an emergency power system or central battery, lasting at least one hour. The 2021 model text raises this to at least three hours and adds MS 2687.
  • Under by-law 253, emergency lighting and power must take over within 60 seconds of a mains failure, from a battery able to carry the load for at least 1.5 hours or from a generator set that starts automatically.
  • Note 1 to the factory rows of Selangor's Tenth Schedule adds that factories operating after dark must provide emergency lighting as Bomba requires.

Registered products from 2026

Under the Fire Services (Fire-fighting Equipment or Fire Safety Installation) Regulations 2026, P.U.(A) 46/2026, in force since 3 February 2026, exit signs, emergency lights, fire resistant doors and fire roller shutters are among 28 products that must be registered with Bomba. Section 36K of the Act, added by the Fire Services (Amendment) Act 2025, makes installing or selling an unregistered prescribed product for installation an offence carrying a fine of up to RM500,000, up to five years' jail, or both. When you replace a sign, light or fire door, ask the supplier for proof of registration.

What about mezzanines, upstairs offices and upper floors?

  • Mezzanines and open staircases (by-law 170). People may leave a mezzanine by an open staircase to the floor below only if a fire anywhere in the compartment would be obvious to people on every level, the travel distances are not exceeded, only 50% of the mezzanine's occupants are assumed to use the open stair (with storey exits on each level for the other 50%), and the main floor's exits are sized for its own people plus 50% of those coming down. Our mezzanine approval guide covers the council and Bomba approvals.
  • Enclosed staircases (by-law 189). In a building of four storeys or more, or where the highest floor is more than 12 m above ground, every staircase used as an alternative escape route must be enclosed in fire resisting construction. Most single and double storey factories fall below this; flatted factory blocks often do not.
  • External staircases (by-laws 190 and 191). A permanent external staircase counts as an exit if it meets the internal staircase rules and is separated from the building by walls and a fire door of the same fire resistance, with no openings in the adjacent wall within 2 m horizontally and 9 m below it (toilet ventilation excepted).
  • Two storey factories. A second floor brings in its own staircases, width checks and sprinkler thresholds; see single storey vs double storey factory.

What should be done if a factory's fire protection system does not meet requirements?

Read Bomba's notice or inspection report line by line and note its deadline. Remove hazards you can fix at once, such as blocked or locked exits. For the rest, appoint a professional engineer or architect to design the fix and submit plans to Bomba before work starts, use a Bomba-registered contractor and registered products, and ask Bomba to re-inspect before the deadline.

What Bomba can do under the Fire Services Act

The Act's definition of "fire-hazard" in section 2 includes an unlawful alteration that makes escape materially more difficult, missing fire equipment the law requires, fire equipment or installations "not in efficient working order", and "inadequate means of exit from any part of a building". Each of these can lead to the steps below.

Stage Section What it means for the owner or occupier
Fire certificate inspection fails 29(5) Bomba serves a notice listing requirements to meet within a set time before the certificate can be issued
Facilities become inadequate while a certificate is in force 32(4), 32(5) Bomba directs the occupier to fix them and may cancel the certificate; ignoring the direction is an offence
Fire-hazard abatement notice 8 Served on the occupier if the occupier caused the hazard, otherwise on the owner; it sets a period and may specify the work
Notice not complied with 10 Fine of up to RM5,000, up to three years' jail, or both, plus RM100 for each day the offence continues after conviction
Bomba does the work 11, 16 Bomba may carry out the work itself and recover the cost in court from the person served
Urgent danger 12, 17 Bomba may do the work at once and recover the cost
Closing order 13 If the notice is ignored and the hazard is likely to recur, Bomba may ask a court to prohibit the risky use
Prohibitory order 35 Where the risk is so serious that use should stop until it is reduced, a court may prohibit or restrict use; breaching the order carries up to RM10,000, up to five years, or both
Order to cease activity 35A In urgent cases Bomba may order the activity to stop without first going to court
No fire certificate for designated premises 33 The owner commits an offence carrying up to RM50,000, up to five years, or both, as amended by Act A1568

Enforcement is real but usually starts with a notice. The housing and local government minister said JBPM inspected more than 21,000 buildings last year and issued 11,260 notices to premises owners, with legal action only when owners fail to comply within the period set (Utusan Malaysia, 9 February 2026). Penang's Bomba director listed obstructed emergency exits and malfunctioning emergency doors among the common failures at inspections (The Star, 1 June 2026).

Step by step

  1. List every item in the notice or report, with its deadline. Separate housekeeping (blocked aisles, locked doors, dead exit sign bulbs, fire doors wedged open) from works (new exits, staircases, sprinklers, pumps, tanks, alarm upgrades).
  2. Fix housekeeping the same day. These need no plans, and they are exactly what the "inadequate means of exit" limb of the Act targets.
  3. Find the approved plans and the year of approval. They show which by-law version applies and whether the problem is a defect or a later change, such as a mezzanine, partitions or a new process.
  4. Appoint the designer. A principal submitting person under the by-laws is a professional architect, professional engineer or building draughtsman; for fire systems you want a professional engineer in mechanical and electrical work.
  5. Submit before you build. Selangor's by-law 245 requires plans, drawings and calculations of all fire fighting installations to go to Bomba before work starts. New openings, staircases or structure also need council building plan approval.
  6. Use registered people and products. Since 3 February 2026, installing, testing, servicing or repairing prescribed equipment (fire extinguishers, gas suppression, fire alarm panels, fire fighting pumps and fire roller shutters) needs a Bomba-registered competent person or fire safety contractor under section 36D and P.U.(A) 39/2026; doing it unregistered carries a fine of up to RM50,000, up to three years, or both.
  7. Test, then ask for re-inspection before the deadline, and keep the commissioning reports, as-built drawings and service records together.
  8. Running out of time or disagreeing? Write to the issuing office before the deadline. Selangor's by-law 255 lets the council extend the time for Parts VII and VIII or allow variations, with an appeal to the State Authority within 30 days. A refusal or conditions on a fire certificate can be appealed to the Minister within 21 days (section 34), and closing or prohibitory orders to the High Court within 10 days (sections 14 and 36).

Your duty as an employer

Section 15(2)(d) of the Occupational Safety and Health Act 1994 requires an employer, so far as is practicable, to provide and maintain safe means of access to and egress from the workplace, and section 19 sets a fine of up to RM500,000, up to two years' jail, or both. Under section 18(2), anyone whose contract or lease makes them responsible for maintaining the means of egress is treated as having control of it, so the lease matters.

Technician fitting an emergency light above a factory exit while pallets are moved away
IllustrationTechnician fitting an emergency light above a factory exit while pallets are moved away

How much does it cost to upgrade a factory's fire protection system?

There is no official price list. The cost depends on which row of the Tenth Schedule your floor area and use fall into, what is already installed and working, whether water tanks, pumps and emergency power must be added, how many exits, staircases or fire doors must be built, and the fees of the engineer and the Bomba-registered contractor. Get itemised quotes after a survey.

What drives the cost

Cost driver Why it moves the bill What to check
Floor area and use Crossing a Tenth Schedule line (for example above 2,000 m² for a single storey factory, or above 1,000 m² or 7,000 m³ for a combustible goods warehouse) brings in sprinklers on top of hose reels Approved floor area against your actual use
What is already there Repairing a working system costs far less than adding one Last test reports, pump set on automatic, valves open
Water and pumps Fire pumps must run on an emergency supply that takes over within 60 seconds (by-law 253), and section 22 of the Act lets Bomba direct an owner in writing to provide water storage for fire fighting Tank, pump room and emergency supply on the approved plans
Hydrants Selangor's by-law 225(2) requires at least one hydrant within 45 m of the fire brigade access and hydrants no more than 90 m apart; in September 2026 the Selangor fire department said work at a burning Jalan Besar Kapar wood factory was delayed because there were no hydrants at the location (The Star, 3 September 2026) Hydrant positions and distances on site
Escape works New door openings, external staircases or fire rated walls are building works with structural design and council approval Whether exits can go in existing walls
Storage height and goods Higher racking or more combustible goods than the design basis can need a different sprinkler design Design hazard and storage height in the M&E report
Registered products and contractors Only registered products and, for prescribed equipment, registered contractors may be used from 2026 Registration certificates in the quote
Professional and approval work Plans to Bomba under by-law 245 and to the council for building works Scope of the engineer's and architect's appointment

The fixed fees you can check

Government fees are small next to the works. The JBPM inspection and test request form on DBKL's One Stop Centre page lists, under P.U.(A) 207/1977, RM100 for a second inspection of new, extended or renovated buildings and test fees such as RM0.50 per sprinkler head, RM50 per pump, RM2 per fire alarm point and RM20 per alarm panel. The fire certificate fees are in our fire certificate guide. Registering a product costs its applicant RM500 under P.U.(A) 46/2026, a cost that sits with the supplier.

Who pays in a rented factory?

The law decides whom Bomba pursues, not who pays. Section 8 points the notice at the occupier when the occupier caused the hazard and otherwise at the owner, and the lease should follow the same logic: the landlord hands over exits, doors, signs, lights and base systems that match the approved plans, and the tenant pays for changes its own layout, racking or process makes necessary. Our partner Ms Teh's guide to fire protection in a Klang factory or warehouse sets out how Klang leases split it.

Does an older factory have to be upgraded to today's rules?

Not automatically. Selangor's by-law 254 required certain existing buildings (places of assembly, shops, offices, other residential buildings, buildings above 18.5 m and buildings classified as hazardous or special risks) to be altered to meet Parts VII and VIII within one year (up to three storeys) or three years (above three storeys) of the by-laws starting. For an ordinary factory, the version it was approved under is the starting point. Two things change that:

  • Alterations and change of use. New partitions, mezzanines, offices or a different process are new work assessed by the council and Bomba, and the Act treats an unlawful alteration that makes escape materially more difficult as a fire-hazard. Penang's Bomba director warned in June 2026 that renovations and changes of use without matching fire safety improvements raise the risk (The Star).
  • Inadequate means of exit is a fire-hazard under section 2 whatever the building's age, so Bomba can still serve a notice on an old factory whose exits are blocked, locked or too few for how it is used today.

Fire certificates are also changing: JBPM's director-general said owners of 9,451 designated buildings must appoint Fire Safety Managers and Fire Safety Officers from 1 April 2027, and that their annual inspection reports would be assessed for certificate renewal (Malay Mail, 6 October 2026).

Escape checklist before you rent or buy a factory

Check What to ask for or look at Red flag
Approved layout Approved building and fire plans, with year of approval Partitions, mezzanines or offices not on the plans
Number of exits At least two per storey and per compartment, 5 m or more apart Only the loading bay and one office door
Travel distance Walk from the far corners to the nearest exit Long dead end aisles between racks
Door hardware Opens from inside without a key Padlocks, chains, bolts high up
Upper floors Two staircases, or the single staircase exception on the approved plan One narrow stair serving many people
Signs and lights Lit KELUAR signs, emergency lights tested Dead fittings, signs hidden by racking
Fire doors Self closing, not wedged, hold open devices that release on heat Doors propped open, closers missing
Records Fire certificate (if designated), service records, contractor's Bomba registration No records, or notices still open

Our used factory building inspection guide covers the rest of the building.

Jason Low (PEA 1478) covers the Bomba requirements for factories in Rawang and Shah Alam in the same detail.

Frequently Asked Questions

How many emergency exits does a factory need in Malaysia?

At least two separate exits from every storey (by-law 166) and at least two storey exits from every fire compartment, at least 5 m apart (by-laws 167 and 174). More are needed if any point on the floor is beyond the travel distance limit, 30 m for a general factory without sprinklers or 60 m with them, or if the exits are too narrow for the occupant load.

What is the minimum width for a fire exit?

Exits are measured in units of 550 mm, and no access to an exit may be narrower than 700 mm. In a factory one unit serves 100 people through doors to the outside or 60 people on stairs, with the floor counted at 10 m² per person. At least one staircase must be two units wide, though 900 mm is allowed where fewer than 50 people use it.

What is the maximum travel distance to a fire exit in a factory?

For a general or special purpose factory, 30 m without sprinklers and 60 m with sprinklers, with a dead end of no more than 15 m. A high hazard factory is limited to 22 m, or 35 m with sprinklers, and no dead end. In open areas the straight line distance may not exceed two thirds of these limits.

What are the requirements for fire-resistant doors in Malaysia?

Fire doors must have the fire resistance the by-laws set for the wall they sit in, with half an hour as the minimum for protected corridors and lobbies, be built with their frames to MS 1073, and have automatic closers. They may be held open only by a device that releases on heat, never on protected staircases or corridors. Since 3 February 2026 fire resistant doors must also be products registered with Bomba.

What should be done if a factory's fire protection system does not meet requirements?

Clear any blocked or locked exits immediately, then list every item in Bomba's notice with its deadline. Appoint a professional engineer or architect, submit the fire installation plans to Bomba before work, use Bomba-registered contractors and products, and ask for re-inspection before the deadline. Ignoring an abatement notice can lead to fines, Bomba doing the work at your cost, or a court order.

How much does it cost to upgrade a factory's fire protection system?

No official price list exists, so any single figure would be a guess. The bill depends on the Tenth Schedule row your factory falls into, what is installed and working, whether tanks, pumps and emergency power are needed, and how much building work new exits require. Bomba's own test and inspection fees are small; get itemised quotes from registered contractors after an engineer's survey.

Can a factory lock its emergency exit doors?

Not in a way that stops people getting out. By-law 173 requires every exit door to open from the inside without a key or any special knowledge or effort, and door holders must release on power failure or fire alarm. Penang's Bomba director listed obstructed exits among the common failures at inspections, and inadequate means of exit is a fire-hazard under the Act.

What are the new fire regulations in Malaysia?

From 3 February 2026, prescribed fire equipment may be installed, serviced or repaired only by Bomba-registered competent persons or fire safety contractors, and 28 product types, including exit signs, emergency lights and fire resistant doors, must be registered. From 1 April 2027, designated premises must appoint Fire Safety Managers and Fire Safety Officers.