Key Takeaways
- A cleanroom factory in Malaysia is approved around your product, not around the building: NPRA regulates medicines, health supplements, traditional medicines and cosmetics, and the Medical Device Authority (MDA) regulates medical devices.
- For medicines, supplements, traditional products and cosmetics, NPRA expects a layout approval before you build. The processing fee is RM1,000 for a new manufacturing site and RM500 to revise an existing layout, which includes upgrading a production floor to a cleanroom.
- Only sterile medicines have fixed cleanroom grades (A, B, C and D under the PIC/S GMP Guide). Tablets, creams, cosmetics and most devices get a cleanliness level justified by product and process risk, which your GMP consultant proposes and the inspector or auditor checks.
- Cleanroom air handling runs around the clock. WHO guidance says air handling units should not be switched off at night or at weekends, and PIC/S sets requalification of grade A and B areas at least every 6 months and grade C and D areas every 12 months. Power, plant space and ceiling void decide which buildings can convert.
- NPRA approvals and the ISO 13485 certificate that MDA requires are tied to the factory address. Moving means a new layout evaluation, a new inspection or a new CAB audit, so a tenant needs a long lease, written consent for alterations and agreed reinstatement terms.
Who regulates a pharmaceutical, medical device or cosmetic factory in Malaysia?
The product decides the regulator, and the regulator decides how much the building must do. Put your product in one of these rows before you view a single unit.
| Product | Regulator | GMP standard used at inspection | Licence or approval | What it means for the building |
|---|---|---|---|---|
| Pharmaceuticals, including APIs | NPRA | PIC/S Guide to GMP for Medicinal Products | Manufacturer's Licence after a pre-licensing inspection | Layout approval before building; fixed grades for sterile products |
| Traditional medicines and health supplements | NPRA | GMP Guideline for Traditional Medicines and Health Supplements | Manufacturer's Licence after a pre-licensing inspection | Layout approval before building |
| Cosmetics | NPRA | Guideline for Cosmetic GMP | No manufacturer's licence at present; each product is notified and a new local maker gets an initial inspection | Layout approval before building; clean, defined areas rather than a graded cleanroom |
| Medical devices | MDA | MS ISO 13485:2017 or ISO 13485:2016, certified by a CAB registered with MDA | Establishment licence under the Medical Device Act 2012 (Act 737) | Work environment set by your device and process; the certificate carries your address |
NPRA lists which GMP guideline applies to each product type in Appendix 27 of its Drug Registration Guidance Document (July 2026 revision). Its GMP inspection FAQ confirms that cosmetics makers currently need no Manufacturer's Licence but must still comply with GMP, and MDA's establishment licensing guidance requires manufacturers to be certified to ISO 13485.
The building also needs its ordinary approvals. NPRA's FAQ says the premises should be licensed by the local council, the Department of Environment and/or the Fire and Rescue Department (Bomba), and an application for a Manufacturer's Licence must include a copy of the valid business licence issued by the local authority for the premises.
This guide explains rules that affect property decisions. It is not legal or regulatory advice: confirm your route with NPRA or MDA and a GMP consultant before you sign.
Medicines, supplements and traditional products: what happens in which order
- Layout evaluation. Submit the proposed layout and process flow to NPRA's GMP Section with the application for the evaluation of manufacturing plant layout. Under DRGD Appendix 27, a new manufacturing site needs a new premises layout (processing fee RM1,000), while a new line, a new production block or upgrading a production floor to a cleanroom needs a revised layout (processing fee RM500).
- Council and Bomba approvals. NPRA's pre-licensing inspection guidance says the quality system is set up after the layout approval and the approvals from the local authority and Bomba.
- Build and set up. Build to the approved layout, install and calibrate equipment and utilities, map warehouse temperatures and write the procedures.
- Inspection. Apply through NPRA's QUEST system with a Site Master File and the layout approval letter. NPRA's inspection fee circular for local premises charges RM1,000 for an inspection of up to one working day, RM1,000 per inspector per working day beyond that, and RM10,000 at most.
- Licence. The Manufacturer's Licence processing fee is RM1,000. NPRA approves a complete application within 4 working days, and each licence runs until 31 December of that year.
Cosmetics: no manufacturer's licence, but the factory is still inspected
There is no cosmetic factory licence in the pharmaceutical sense today. Even so, NPRA's pre-licensing guidance makes the layout evaluation compulsory for new cosmetics manufacturers and inspects a new local maker before its products are notified. The Cosmetic GMP guideline asks for defined areas for receiving, sampling, quarantine, weighing, processing, bulk storage, packaging, finished goods and equipment washing, plus smooth walls and ceilings, cleanable floors, trapped drains, adequate ventilation and a laboratory separated from production. It does not set a cleanroom grade.
Medical devices: ISO 13485 and an establishment licence
Under Act 737, manufacturers, authorised representatives, importers and distributors all need an establishment licence. A manufacturer pays an RM250 application fee and an RM4,000 licensing fee (RM200 and RM2,000 on renewal) and must apply for renewal at least 90 days before expiry. The address matters: if you move, the CAB must audit the new premises and reissue your ISO 13485 certificate and audit report with the new address before MDA records the change.
Which cleanroom class does your product need?
Only sterile medicines have grades written into the GMP rules. Everything else gets a cleanliness level justified by risk.
Sterile medicines: grades A to D
The PIC/S GMP Guide annexes (PE 009-18, 24 September 2026), whose Annex 1 covers sterile products, set four grades and the maximum particle counts used to classify them:
| Grade | Typical use | Max particles of 0.5 µm or larger per m³, at rest | In operation |
|---|---|---|---|
| A | Aseptic filling, exposed sterile components | 3,520 | 3,520 |
| B | Background room for grade A in aseptic work | 3,520 | 352,000 |
| C | Preparing solutions to be filtered; filling terminally sterilised products | 352,000 | 3,520,000 |
| D | Preparing solutions and components before filling or sterilisation | 3,520,000 | Set by the manufacturer |
Annex 1 says products that are terminally sterilised should be filled in at least grade C, and aseptic preparation and filling takes place in grade A with a grade B background unless an isolator is used.
ISO classes and the old "Class 100,000" names
Cleanroom contractors quote ISO 14644-1 classes and sometimes the older US class names. The US FDA aseptic processing guidance gives the match: ISO 5 is Class 100 (3,520 particles of 0.5 µm or larger per m³), ISO 6 is Class 1,000 (35,200), ISO 7 is Class 10,000 (352,000) and ISO 8 is Class 100,000 (3,520,000). It also notes that ISO 5 approximately equals EU Grade A.
Non-sterile medicines, cosmetics and devices
For tablets, capsules, powders, liquids, creams and ointments, the WHO HVAC guideline for non-sterile products says the level of air cleanliness is set by the product, the process and its susceptibility to degradation, and that any classification must state whether it applies as built, at rest or in operation. Cosmetics follow the Cosmetic GMP premises rules above. For devices, the MDA guidance sets the ISO 13485 requirement but no single cleanroom class, so the class follows your device, process and sterilisation route and is checked at your CAB audit.
What to check before shortlisting: ask your GMP consultant for a room list with the grade or class, pressure, temperature and humidity of each room. That list sizes the air handling plant, and the plant decides which buildings work.
What air conditioning and filtration does a GMP cleanroom need?
A cleanroom is not just an air-conditioned room. It needs air handling units (AHUs) that filter, cool and dehumidify the supply air, deliver a set volume into each room and hold each room at a set pressure against its neighbour.
| Element | What the guidance says | What it means for the building |
|---|---|---|
| Filtration | WHO: HEPA filters used against cross-contamination should be at least H13 under EN 1822 | Space for filter housings and access to change them |
| Pressure | PIC/S: adjacent rooms of different grades at least 10 Pa apart (guidance value); FDA: 10 to 15 Pa | Tight walls and ceilings, airlocks, self-closing doors |
| Air changes | FDA: at least 20 air changes per hour is typically acceptable for ISO 8 supporting rooms, and significantly more for ISO 7 and ISO 5 | Larger AHUs and ducts as the class tightens |
| Outside air | WHO: facilities normally kept at positive pressure to outside, with no infiltration of unfiltered air | A sealed envelope and a sound roof over production |
| Temperature and humidity | WHO: limits set for the materials and products, then controlled and recorded | Cooling and dehumidifying capacity |
| Monitoring | PIC/S: pressure indicators between cleanrooms; critical pressures monitored continuously with alarms | Sensors and a building management system |
| Operating hours | WHO: avoid switching AHUs off overnight or at weekends | 24-hour power and a plan for outages |
| Requalification | PIC/S: grade A and B every 6 months at most, grade C and D every 12 months | A recurring testing budget |
Two property points follow. First, power: a cleanroom plant draws power day and night, so check the existing TNB supply and the time an increase takes, explained in our guide to TNB power upgrade costs. Second, space: AHUs sit on the roof, on a platform or in a plant room, and ducts run in a void above the cleanroom ceiling, so the clear height of the shell must allow for both.
What does converting an existing factory into a cleanroom involve?
Converting a factory is a design, approval and qualification project, not a renovation. A typical sequence:
- Fix the product, process and room list with a GMP consultant: grades, pressures, temperature, humidity and the flows of people, materials and waste.
- Screen the building: zoning and approved use, CCC, power, roof load or plant space, floor slab, clear height, water supply, drainage and effluent route, flood history and neighbours.
- Get the layout approved by NPRA (medicines, supplements and cosmetics) or agreed with your CAB (devices) before construction.
- Get local council and Bomba approvals for the works.
- Build: wall and ceiling panels, sealed floor, AHUs and ducts, HEPA filters, airlocks, pass boxes, purified water and compressed air where needed, and monitoring.
- Qualify: WHO says HVAC qualification follows a master plan, and PIC/S lists cleanroom classification, filter integrity, airflow volume, pressure differences and air velocity as the minimum tests.
- Apply for inspection, then the licence or product notification.
Buying a plant that already holds GMP status is not a shortcut on its own. NPRA's pre-licensing guidance says a new owner must not rely solely on claims about the facility's GMP status and should assess it, and a major layout change needs a new layout evaluation. Our earlier piece on GMP pharma and medical device factories in Selangor explains why old wet-process plants such as glove factories rarely suit sterile work.
How much does it cost to convert a factory to a cleanroom?
There is no official rate per square foot, and we will not guess one. The cost moves with the grade and area of each room, AHU capacity, utilities such as purified water, the power upgrade, the condition of the shell and the qualification work. What is fixed are the regulator fees:
| Item | Fee | Source |
|---|---|---|
| NPRA layout evaluation, new site | RM1,000 | DRGD Appendix 27 |
| NPRA layout revision, including upgrading to cleanroom | RM500 | DRGD Appendix 27 |
| NPRA GMP inspection, local premises | RM1,000 for up to one day; RM1,000 per inspector per day beyond; RM10,000 maximum | NPRA fee circular, 2008 |
| NPRA Manufacturer's Licence processing | RM1,000 each year | DRGD Appendix 28 |
| MDA establishment licence, manufacturer | RM250 application plus RM4,000 licensing | MDA/GD/0027 |
When you collect quotes, ask each contractor to split the price into panels and doors, HVAC and ducting, filters, electrical and power upgrade, utilities, monitoring and qualification, and to state the AHU power draw, the filter replacement schedule and the cost of each requalification. That turns one lump sum into figures you can compare and negotiate.
What should a tenant check in the lease of a cleanroom factory?
Start with the term. The NPRA licence covers the premises named in it, a new manufacturing site needs a new layout plan, and an MDA licensee who moves needs a new CAB audit. Leaving after a short lease means repeating approvals and qualification, so put these in writing before you sign:
- Term and renewal long enough to recover the fit out, with renewal options. Terms over three years are granted as registered leases; see our factory lease term guide.
- Landlord consent for alterations: roof openings and AHU platforms, wall and ceiling panels, drains, generator, extra power and any council or Bomba submission that needs the owner's signature.
- Reinstatement: whether the cleanroom may stay at the end, who owns the panels and plant, and what must be removed. Our reinstatement guide explains the clauses.
- Owner documents for your submissions: title, approved building plans and CCC, which the council licence and the NPRA application rely on.
- Access for inspectors and round-the-clock operation, since the HVAC never stops.
- A sale of the building: ask for the sale to be subject to your tenancy, and for an option to buy when the fit out is large.
Which factory buildings are easiest to convert to GMP?
The strongest candidates are detached or semi-detached factories with a clear span, enough height for a ceiling void, room on the roof or ground for AHUs, a power supply that can grow, separate loading for incoming materials and finished goods, space for a QC laboratory and clean neighbours. The Cosmetic GMP guideline opens its premises chapter with protection from contamination from the surroundings and pests, and WHO says unfiltered air should not leak in, so avoid units beside dusty, smoky or odorous operations and buildings with a leaking roof. Filter candidates by power, height and land size with find factory by specs.
Food factories and electronics plants follow different rules from these, and we cover them in separate guides.
Practical steps: more questions
How long does NPRA GMP approval take for a new factory?
NPRA does not publish a single timeline for the whole process, because it depends on how quickly you build, qualify and become ready for inspection. The fixed steps are layout approval before building, inspection when you are ready, and a licence decision within 4 working days of a complete application. Plan the lease or purchase around the construction and qualification period, not the licence step.
Can I buy a factory that already has GMP approval and start producing?
The building helps, but the approval belongs to a manufacturer and its quality system. NPRA says a new owner must not rely on claims about the facility's GMP status and should assess it, and major layout changes need a new layout evaluation. You still need your own inspection, licence and product registration or notification.
Frequently Asked Questions
Where can I rent a factory suitable for pharmaceutical manufacturing?
There is no ready list of GMP factories for rent, and very few FactoryHub listings mention GMP or cleanrooms, so most pharma makers rent a suitable shell and build controlled rooms inside. FactoryHub's guides point to Rawang, Shah Alam, Subang Jaya, Bangi and Sepang in Selangor. Look for a detached or semi-detached factory with clear span, height for a ceiling void, room for air handling units, power that can grow and clean neighbours, and take a long lease, because NPRA approvals are tied to the address.
What type of factory do I need for medical device production in Malaysia?
Usually a detached or semi-detached factory on industrial land that can take a controlled or clean room inside; your device and process decide the rest. MDA requires every manufacturer to hold an establishment licence and ISO 13485 certification, and the certificate carries the factory address, so moving means a new audit. In Selangor, device suppliers such as packaging, component and contract assembly firms mostly use mid-size detached factories. Check the ceiling height, round-the-clock power for air handling and separate loading for materials and finished goods.
Do I need a licence to start a cosmetic factory in Malaysia?
Not a manufacturer's licence: NPRA says cosmetics makers currently do not need one and may manufacture once a product is notified. The factory must still follow Cosmetic GMP, have its layout evaluated by NPRA and pass an initial inspection as a new local manufacturer. You also need the council business licence and, where required, Bomba and DOE approvals.
Can a pharmaceutical company rent a factory instead of buying one?
Yes, the NPRA rules do not require you to own the building, but the licence and approved layout are tied to the address. Moving to another factory means a new layout evaluation, a new inspection and new qualification work. A tenant should therefore secure a long term with renewal options, written consent for the cleanroom works and agreed reinstatement terms.
Who builds cleanrooms in Malaysia?
Specialist cleanroom and HVAC contractors design and build the panels, air handling and monitoring, usually to a room list prepared by a GMP consultant. The contractor does not approve anything: NPRA approves the layout and inspects the factory, or the CAB audits a device maker. Include qualification documents and test reports in the contractor's scope.
What is the difference between an ISO 7 and an ISO 8 cleanroom?
ISO 7 allows up to 352,000 particles of 0.5 µm or larger per cubic metre and ISO 8 up to 3,520,000, according to the class table in the US FDA aseptic processing guidance. ISO 7 used to be called Class 10,000 and ISO 8 Class 100,000. The cleaner class needs more air changes, which means larger air handling units and more power.
Can I use normal split air conditioners in a GMP production room?
Not in a graded cleanroom. A standard split unit only cools and recirculates room air, while a cleanroom needs filtered supply air at a controlled air change rate and a pressure difference to the next room. For cosmetics and some non-sterile areas the guidelines ask for ventilation suited to the operation rather than a grade, so confirm the design with your GMP consultant and during NPRA's layout evaluation.
Does a medical device factory need a cleanroom?
It depends on the device and on how it is made and sterilised. MDA requires manufacturers to hold ISO 13485 certification from a CAB registered with MDA, and the work environment is part of that quality system. Your quality team sets any cleanroom class from the device risk and process, and the CAB audits it.
FactoryHub is dedicated to helping every client find the right factory or warehouse. For a building that can take a cleanroom conversion, send us your room list, power requirement, built-up area and preferred location: Peter Tan (REN 12771) at 016-666 6872 or Jason Low (PEA 1478) at 012-288 1834, registered with BOVAEP under CID Realtors Sdn Bhd.