Key Takeaways

  • Testing work for the data centre supply chain (server and rack burn-in, UPS checks, battery and BESS cycling) puts a lot of power into a small floor. One liquid-cooled AI rack is specified by HPE at 132 kW nominal, about 200A at 400V on our conversion, and HPE advises data centres to provision about 192 kW for its peak.
  • Small factories rarely come with that power. Under TNB's handbook, a supply above 350 kVA (about 505A) needs a new substation, and the land for it is handed to TNB. On a terrace lot with a registered median land area of 2,002 sq ft, a 7m x 5m compact substation plot takes nearly a fifth of the land, and only the owner can give it.
  • TNB's typical lead time is under 3 months when no substation is needed and 3 to 12 months when one is, so the fastest route is a unit whose intake is already energised at the amps you need.
  • Amps are only the first filter. Check heat removal (servers turn essentially all their power into heat), floor loading under racks and battery cabinets, a switchboard with spare outgoing ways, and fire approvals before any lithium battery arrives.
  • The other demand in KL and Selangor follows the money MIDA approved in the first half of 2026: data centres and digital services, E&E and semiconductors, machinery, battery storage, port logistics and food manufacturing.

Peter Tan and Jason Low are seeing a pattern in their 2026 enquiries: more firms in the data centre supply chain asking to rent a factory for testing, with a small built-up area but a high incoming power supply. Typical uses are server and rack burn-in before delivery, UPS and switchgear checks, and battery or energy storage (BESS) testing. This guide is for anyone looking for a high power factory for rent in Selangor for that kind of work. It explains why the combination is scarce, how many amps the work really needs, what else the unit must have, who pays when the supply has to be upgraded, and what to put in your brief.

It does not repeat what other FactoryHub guides cover. For running a data hall inside a factory, see how many amps a data centre needs. For switchgear, busduct and cooling suppliers, see data centre supplier factories in Banting and Dengkil. For battery production lines, see EV and battery factories, and for storing cells and packs, see lithium battery and dangerous goods warehouses. This guide explains rules in general terms and is not legal advice.

Why is a small factory with high power so hard to find in Selangor?

Because power in Malaysia is planned around the lot, not the floor area. TNB's own supply table puts three-phase whole-current supply at up to 72kVA (100A) maximum demand, with CT-metered 400V supply above that up to 1,000kVA. Most terrace and cluster factories were built for light assembly and storage, and were wired at the low end of that range.

The step that stops a small unit is the substation. TNB's Electricity Supply Application Handbook (ESAH 3.1) feeds any maximum demand above 350 kVA (about 505A at 400V) by direct cable from a new substation. As our TNB substation guide sets out, the substation land is transferred or leased to TNB for a nominal RM10, a compact substation needs a standard 7m x 5m plot, and TNB wants it at the front of a fenced factory with its own access.

Run that against a terrace lot. JPPH-registered terrace factory sales in Shah Alam, Klang and Port Klang, and Puchong all show a median land area of 2,002 sq ft. A 7m x 5m plot is 35 m², about 377 sq ft, or nearly a fifth of that lot (our arithmetic). Few owners of a small lot will give that up, and a tenant cannot: the TNB application includes the title copy and Borang A for the substation land, and only the registered owner can transfer or lease that land.

So high amps tend to sit on detached and large semi-D lots, which come with more built-up area than a testing team needs. That mismatch is the whole problem, and it is why the best units are often existing high-power factories that already carry a substation.

How many amps does battery, UPS or server testing really need?

It depends on what runs at the same time. The conversions below use the rule of thumb on our high-power factory page: at 400V three-phase, 1,000A gives roughly 600 to 650 kW of usable load, or about 0.65 kW per amp.

Server and rack burn-in

Rack builders burn in servers, running them under load before shipping. Supermicro, for example, describes a 1-megawatt rack-level burn-in facility at its factory. Rack power varies widely:

What is under test Power per rack (source) Approx. amps at 400V (our conversion)
Typical data centre rack 7.8 kW average, excluding new high-density sites (Uptime Institute 2026) About 12A
Liquid-cooled AI rack, nominal 132 kW TDP (HPE QuickSpecs) About 203A
Same rack, peak to provision for About 192 kW (HPE) About 295A

Four AI racks burning in together at 132 kW is 528 kW before cooling. If cooling and losses add 30 to 50% (the PUE 1.3 to 1.5 range our data centre guide uses), the total is about 686 to 792 kW, roughly 1,050A to 1,220A. That is a high-power factory brief on a floor area that can be a few hundred square feet.

Battery, UPS and BESS testing

Battery test systems are sold by power. One maker lists pack test systems at 60 kW to 300 kW, and some of these regenerative systems feed discharge energy back to the grid. That cuts the electricity bill, but the intake still has to carry the charging peak of whatever runs at the same time. One 300 kW tester at full charge power is about 460A on our conversion.

Utility-scale units are a different order. TAMCO's Shah Alam facility is to assemble Hoymiles' 5MWh and 6MWh liquid-cooled BESS units. Charging one 5MWh unit over four hours would draw about 1.25 MW, close to 1,900A at 400V (our arithmetic), which is above the roughly 1,440A point where TNB moves supply to 11kV. Unless the unit already has an 11kV intake, such systems can only be tested at reduced power, so agree the test profile with your engineer first.

The Energy Commission's BESS Safety Guidelines (GP/ST/No.62/2026) explain why this testing exists: a Factory Acceptance Test must verify BESS components before installation, with a FAT certificate listing every component tested. The guideline names IEC 62619 and IEC 63056 for battery systems, IEC 62477-1 for power conversion, UL 9540A for thermal runaway and UN 38.3 before transport.

Work out your own number

  1. List every tester, rack, load bank, chiller and air conditioner that can run at the same time.
  2. Add their rated kW, then add cooling if it is not already in the list.
  3. Divide by 0.65 to get amps at 400V, then add headroom for growth.
  4. Check it with the factory power calculator and your electrical consultant before you view.
Small factory unit with a substation feeding server racks, battery cabinets and a load bank under test
IllustrationSmall factory unit with a substation feeding server racks, battery cabinets and a load bank under test

What else must the unit have besides amps?

Heat removal and ventilation

Schneider Electric's White Paper 25 states that the power IT equipment draws is essentially all converted to heat, and gives 1 ton of cooling as 3,530 W. A 132 kW rack under burn-in is therefore about 37 tons of heat (our arithmetic). Liquid-cooled racks pass that heat to a coolant unit, and HPE's in-row CDU for this rack is rated for 1.3 MW of cooling and takes a three-phase 380 to 480V supply, so you also need yard or roof space for dry coolers or chillers. For battery rooms, the BESS guideline requires HVAC or equivalent to keep temperature-sensitive parts within limits.

Floor loading

HPE gives the fully loaded rack at about 3,245 lbs (about 1,472 kg) on a 600mm x 1,068mm footprint, roughly 2.3 tonnes per m² under the rack (our arithmetic). Battery cabinets are heavy too. Ask for the slab's design load in writing and test it with the floor loading calculator.

Switchboard, earthing and who does the work

Check the main switchboard rating, spare outgoing ways and the earthing system, not just the figure in the advert. Under ESAH, any application above 100A goes to TNB through an Electrical Consultant Engineer registered with the Board of Engineers Malaysia, and the BESS guideline requires electrical work by a contractor registered with the Energy Commission.

Fire, Bomba and lithium batteries

Under the Fire Services Act 1988, every designated premises needs a fire certificate, renewable annually. The BESS guideline recommends installing BESS outdoors; where indoor installation is unavoidable, fire suppression must be provided and Bomba's requirements met. Ask the landlord for the current fire certificate and tell your fire engineer how many kWh of lithium will be inside at any time. Storage of cells and damaged returns is covered in our lithium battery warehouse guide.

Zoning and licences

Testing and burn-in are industrial activities, so confirm that the title and the council's planning allow them and that the unit's CCC covers the building as it stands, and allow time for the council licence for your business at that address.

Who pays for a power upgrade in a rented factory, and how long does TNB take?

The applicant pays TNB. As our substation guide sets out from TNB's charge book, low-voltage CT-metered supply carries a connection charge from RM4,050 (61 to 90 kW) to RM38,250 (721 to 850 kW), medium voltage is RM45 per kW of declared demand, and an upgrade pays the difference between the new and existing load charge. Cable trenching, switchgear and consultant fees come on top.

Supply (ESAH 1.3.5) Typical TNB lead time
400V, no new substation Less than 3 months
400V, with a new substation 3 to 12 months
11kV 6 to 12 months

These assume no delay in local authority approval. In a lease, who funds the upgrade and what happens to it at the end is for the tenancy agreement to settle, so put in writing who applies, who pays, whether the landlord gives substation land, whether rent starts before the power is live, and whether you must reinstate at the end.

Where in Selangor should you look, and should you rent or buy?

Most high-power units sit in the Port Klang belt, followed by Kapar, Shah Alam and Telok Panglima Garang. For firms serving data centre sites around Cyberjaya, Dengkil and Banting, Puchong sits closest, and the supplier arc in our supplier guide runs on from Shah Alam to Dengkil, Jenjarom and Banting.

JPPH-registered factory rents (24 months to August 2026) give a baseline. They cover all units, not only high-power ones, so a unit with a large energised intake can rent above them.

Area Registered median rent By type
Shah Alam RM1.71 psf/month (119 tenancies) Terrace RM1.79, semi-D RM2.12, detached RM1.50
Klang & Port Klang RM1.43 psf/month (780 tenancies) Terrace RM1.47, semi-D RM1.78, detached RM1.22
Puchong RM2.14 psf/month (49 tenancies) Terrace RM2.18, semi-D RM2.65
Telok Panglima Garang & Jenjarom RM1.45 psf/month (58 tenancies) Detached RM1.51

Rent while contracts are short or the test volume is unproven, and the typical registered term is 24 months. Buy, or build on land, once you are paying for a substation, cooling plant and fire systems that a landlord will not refund. If you want to see what is on the market at your amps, including units not advertised, start from high-power factories in Selangor.

Port, small factories with power pylons and data centre buildings linked by one highway in Selangor
IllustrationPort, small factories with power pylons and data centre buildings linked by one highway in Selangor

What should you put in the brief to an agent?

  • Peak load in kW and amps at 400V, with your equipment list, and whether it runs around the clock.
  • Built-up area you actually need, and the minimum you will accept if the power is right.
  • Cooling method (air, liquid, chilled water) and outdoor space for chillers or dry coolers.
  • Floor loading needed under racks or battery cabinets, in tonnes per m².
  • Maximum kWh of lithium on site at once, and whether damaged batteries come back.
  • Loading needs: dock height, forklift, crane, and the size of the crates or containers.
  • Lease term, start date, and whether you will fund a supply upgrade.

Which other industries are driving factory and warehouse demand in KL and Selangor now?

MIDA's first-half 2026 figures are the backbone. Selangor led the states with RM70.0 billion across 835 projects, driven by digital investments. Nationally, manufacturing approvals were RM51.3 billion. Each line below ties a sector to a figure or announcement and the premises it asks for.

Industry What the sources show Premises it asks for
Data centres and digital Data centres and cloud computing were RM95.8 billion of national approvals. A planned data centre at COMPASS @ Kota Seri Langat has 300 MVA power capacity and a 210 MW IT load. The Menteri Besar said power requirements must be cleared by TNB. Land for the halls; small high-power units for testing, spares and service teams
E&E and semiconductors E&E approvals were RM16.6 billion. NXP is adding about 500,000 sq ft of assembly and test space in Petaling Jaya, ramping from the first quarter of 2028. Clean, stable power, good floor flatness, room for cleanroom fit-out
Machinery and equipment RM7.5 billion, up 44.8%. Detached units with crane, height and strong floors
Battery storage and solar ESS investment rose from nearly RM30 million in 2024 to over RM800 million in 2025. LSS6 includes 1,250MW of BESS capacity. High power, fire separation, yard for containers, test bays
Port logistics Port Klang handled a record 15.14 million TEUs in 2025. One Metrohub 3 block at Bukit Raja will include dangerous goods storage, driven by lithium battery imports, due in the third quarter of 2027. Tall warehouses, docks, trailer yards, DG and bonded status
Food manufacturing RM4.9 billion, up 40.9%. Drainage, effluent treatment, cold rooms, halal segregation
Chemicals and transport equipment RM5.5 billion and RM4.9 billion. DOE approvals, bunding, heavy power for presses and lines

The figures by sector are national; only the RM70.0 billion is Selangor's own. The Star noted in August that electricity is the main concern for data centres, which need large, reliable supply around the clock. The same constraint reaches every tenant in the testing chain around them.

Frequently Asked Questions

How many amps do I need to test servers or AI racks in a factory?

Add up everything that runs at once and divide the kW by about 0.65 to get amps at 400V. A typical data centre rack averages 7.8 kW, about 12A, while one liquid-cooled AI rack is specified at 132 kW nominal, about 203A, with a peak of about 192 kW. Four AI racks plus cooling come to roughly 1,050A to 1,220A.

Can I rent a small factory and upgrade the TNB supply myself?

You can apply as the occupier, but above 350 kVA (about 505A) TNB needs a new substation, and its land must be transferred or leased to TNB by the owner. On a small lot the owner often refuses. Agree in the lease who applies, who pays and what happens at the end before you sign.

How long does TNB take to increase power to a factory?

TNB's handbook gives under 3 months at 400V without a new substation, 3 to 12 months with one, and 6 to 12 months at 11kV, assuming no delay in local authority approval. Any load above 100A must be applied for by an Electrical Consultant Engineer registered with the Board of Engineers Malaysia. A unit with the supply already energised avoids the wait.

Do I need Bomba approval to test lithium batteries in a factory?

Designated premises need a fire certificate under the Fire Services Act 1988, renewed every year. The Energy Commission's BESS guideline recommends outdoor installation and, where a BESS must be indoors, requires fire suppression and compliance with Bomba's requirements. Tell your fire engineer the maximum kWh on site before you sign.

Why do testing firms want a small built-up but high amps?

Test racks and battery cyclers are compact but draw heavy, continuous loads, so the bottleneck is power and cooling, not floor area. Paying for a large detached factory only to get its intake wastes rent. The usual compromise is a smaller unit that already has a substation, or part of a larger high-power building.

Where can I rent a high power factory in Selangor?

Most high-power units are in the Port Klang belt, followed by Kapar, Shah Alam and Telok Panglima Garang. Puchong and Shah Alam suit firms serving data centre sites in the Cyberjaya, Dengkil and Banting area. Some owners do not advertise these units, so brief an agent with your amps and size.

What is the rent for a factory in Shah Alam, Klang or Puchong?

JPPH-registered factory rents in the 24 months to August 2026 had a median of RM1.71 psf a month in Shah Alam, RM1.43 in Klang and Port Klang and RM2.14 in Puchong. These cover all units, so a unit with a large energised power supply can rent above them.

FactoryHub is dedicated to helping every client find the right factory or warehouse. For a small, high-power unit for testing, WhatsApp Peter Tan (REN 12771) at 016-666 6872 or Jason Low (PEA 1478) at 012-288 1834 with your amps, size and area.